How to hydraulic calculate a fire sprinkler system

How to hydraulic calculate a fire sprinkler system

This article, 'How to calculate a fire sprinkler system', will demonstrate some of the basics for carrying out fire sprinkler calculations by the long-hand method.

This article will demonstrate some of the basics for carrying out fire sprinkler calculations by the long-hand method with a scientific calculator or our own hydraulic calculator - Hcal2, which you can freely download from our website.  

In this example, we will use three sprinklers and three pipes which would of course be part of a much larger fire sprinkler system. These basic procedures can also be used for calculating many other types of systems, such as fire hydrants, hose reels or the discharge from a water cannon or monitor we can also use the same principle for almost all other water-based fire protection systems as long as we have a k-factor for the output device (fire sprinkler, water mist nozzle and so on).

In this example, we will use a very simple system with three sprinklers and three pipes. this is often called a range or branch pipe, which is part of a larger 'tree system'. A tree system is an 'end feed'. That is, water is only fed from one direction instead of a grid or loop system when water may arrive at the sprinkler head from more than one direction. 

Below is a diagram of the three sprinklers and pipes, which we will calculate.  We have dimensioned the pipe lengths and given each junction point a unique node reference number which we use throughout the calculations. 

3 pipes and fire sprinklers

For each pipe, we need to know the pipe length, internal diameter (ID) of the pipe and the pipe material so we can determine the pipe c-factor, the table below summarises the pipe data which we will need for the calculation for this example: 

Node Ref  Pipe Size ID (mm)  Length (m) C-factor
130-120 27.30 3.20 120
120-110  27.30  3.20  120 
110-100 36.00  3.20  120 


We will also need additional information, such as the type of sprinkler head, the area each head is covering, and the design density for each sprinkler head in the system.

For this example, we will use the following design parameters:

design density: 7.50 mm/min
sprinkler head: K-factor of 70 with a minimum pressure of 0.5 bar
head area: 10.20 m2

In this example, we have kept it very simple and used the same sprinkler head for all three sprinklers, but this may not always be the case, so again, it may be helpful to summarise the information in a table such as this: 

Node Ref  Design Density
(mm/min)
Sprinkler k-factor Sprinkler minimum
pressure (Bar)
Head area (m2)
130 7.50 70 0.5 10.20
120 7.50 70 0.5 10.20
110 7.5 70 0.5 10.20


The first step is to calculate the minimum flow which will be required at the most remote sprinkler, which in this case is at node [130], this is a two-step process as will need to calculate the minimum flow required to satisfy the 7.50 mm/min design density and then find the flow rate from the sprinkler given the sprinklers minimum pressure requirement, whichever is the greater flow will become our initial flow from the first sprinkler at node [130].

We will first calculate the flow given the design density of 7.50 mm/min and the area the head is covering, we do this by multiplying the design density by the head area:

Equation 1:

q1 = (design density) x (area per sprinkler)

In this example, this gives:

          q1 = 7.50 mm/min x 10.20 m2 = 76.50 L/min

The second step is to calculate the minimum flow from the sprinkler given the K-Factor and the minimum head pressure by using the standard K-Factor formula:

Equation 2:

q = kp0.5

Where

p = the required pressure
q = the required flow from the first sprinkler
k = the discharge coefficient of the sprinkler (k-factor)

In this example, this gives:

                q = 70 x 0.50.5 = 49.50 L/min

By comparing the two calculations above, we can see that the minimum flow required from the sprinkler head will be 76.50 L/min as this is the highest flow rate from the two calculations and is required to meet the 7.50 mm/min design density.  We can also see that the minimum sprinkler pressure of 0.5 bar is not sufficient to produce the required flow rate, so the next step will be to determine what pressure will be required to produce the required flow of 76.50 L/min at the first sprinkler head at node [130] we can do this by using equation 3.

Equation 3

                p = (q/k)2

In the example, this gives:

                p = (76.50 / 70)0.5 = 1.194 bar

We have determined the minimum pressure and flow for the first sprinkler at node [130], 76.50 L/min @ 1.19 bar. The next step is to calculate the pressure drop in the pipe between node [130] and [120], and for this, we will use the Hazen Williams pressure loss formula.

Equation 4

 hazen williams pressure loss formula

Where

p = pressure loss in bar per meter
Q = flow through the pipe in L/min
C = friction loss coefficient
d = internal diameter of the pipe in mm

We know that the flow rate from the sprinkler at node [130] is 76.50 L/min, and this will be the flow rate in the first pipe between nodes [130]-[120]. As the pipe has an internal diameter of 27.30 mm and a C value of 120, this will give us:

equation 4 step1

The pressure loss in the first pipe is 0.027 bar/m, and the total pressure loss in the pipe is 0.086 bar. 

We now need to add the pressure loss in the pipe to the start pressure at the sprinkler head at node [130], which was 1.19 bar to find to pressure at node [120] and at the seconded sprinkler head at node [120] this gives us 1.194 + 0.086 = 1.28 bar. 

The next step is to find the flow from the seconded sprinkler head at node [120] to do this, we will use the K-Factor formula

Equation 5

 k factor equation

This gives 70 x 1.2800.5 = 79.20 L/min from the sprinkler head at node [120], which we now add to the flow in the first pipe node [130]-[120] to find the total flow in the second pipe [120]-[110] to find the total flow in the seconded pipe which is 155.70 L/min.

3 3 Sprinkler Man calc

Having found the total flow in the seconded pipe [120]-[110] we can now find the pressure loss in, to do this we will use the Hazen-Williams pressure loss, formula 4 which we used above this gives us:   

Hazen Williams pressure loss calculation

We now add the pressure loss of 0.317 bar to the pressure at node [120] to find the pressure at node [110] this gives us: 0.317 + 1.280 = 1.597 bar

4 3 Sprinkler Man calc

We now need to find the flow from the sprinkler at node [110]. We do this by using the k-factor given in equation 5 as we now know the pressure at node [110] is 1.597 bar, this gives 70 x 1.5970.5 = 88.50 L/min from the sprinkler head at node [110].  We now add this flow to the flow in the second pipe [120]-[110] to find the total flow in the third pipe [110]-[100], which will give us a flow of 244.20 L/min. 

the completed fire sprinkler calculation of the 3 sprinklers

The last step is to find the pressure loss in the third pipe [110]-[100], and again we will use the Hazen-Williams pressure loss formula given in formula 4 above. However, the last pipe has an internal diameter of 36.0 mm, so this gives us the following:

HWF last pipe calculation

We now add the pressure loss in this pipe to the pressure at node [110] to find the pressure at node [100]. This will be 0.189 + 1.597 = 1.786 bar.  We have now completed the calculation for all three sprinkler heads and have found the source pressure and flow required for this system is:

244.20 L/min @ 1.786 Bar

This pressure and flow is often referred to as the source required for the system and is the minimum pressure and flow required for the system for it to be able to provide the required design density (in this example, 7.50 mm/min) at the most remote head [MRH] at node [130]. 

You should also be able to see that only the Most Remote Head has the minimum requirement of 7.50 mm/min design density. All the other sprinklers will have a higher pressure as they are hydraulically closer to the water source, so they will have higher pressure and discharge more water through the sprinkler. This can be seen in the table below: 

Node Ref  min Design Density
(mm/min)
Pressure 
(Bar)
Flow from sprinkler
(L/min)
Head Area
(m2)
Actual
Design Density
 130 [MRH] 7.50 1.194 76.50 10.20 7.50
120 7.50 1.280 79.20 10.20 7.76
130 7.50 1.597 88.50 10.20 8.68


Sprinkler calculation step by step

  1. Calculate minimum flow from the MRH with the sprinkler minimum pressure and k-factor
  2. Calculate the minimum flow given the system design density and sprinkler head area.
  3. If the calculation in step 2 is the highest flow demand, calculate the required head pressure; otherwise, we can use the minimum sprinkler pressure in step 1.
  4. Calculate the pressure loss in the pipe.
  5. Add the head pressure to the pressure loss in step 4 to determine the pressure at the next sprinkler.
  6. Use the k-factor formula to determine the flow from the sprinkler head.
  7. Repeat steps 4 to 6 until you do not have any more sprinklers or pipes.

 

Image